Meanwell PB-600-48: 600 Watt Single Output Lead-Acid Battery Charger.
- Built-in active PFC function PF>0.95
- Protection: Reverse polarity / Short circuit / Over voltage / Over temperature
- Charger for lead-acid batteries
- 3 color LED loading indicator
- Built-in remote ON-OFF control
- Built-in temperature compensation function
- Built-in fan speed control (depends on charging current)
GENERAL SPECIFICATIONS
Input Voltage | 90 ~ 264Vac 127 ~ 370Vdc |
---|---|
Input Frequency | 47 ~ 63Hz |
Power Factor | 0.95/230Vac 0.98/115Vac at full load |
Input Current | 6.8A/115VAC 3.4A/230VAC |
Inrush Current | 25A/115Vac 50A/230Vac |
Leakage Current | <3 .5ma="" 240vac="" td="">3> |
Battery Type | Open & Sealed Lead Acid |
Over Voltage Protection | Shut down o/p voltage, re-power on to recover |
Over Temperature Protection | Automatically derate charge current until zero, recovers automatically after temperature goes down |
Remote Control | Open: Normal work Short: Stop Charging |
Leakage Current from Battery | 1mA |
Fast Charge | 2 / 8 stage select |
Charging OK | Relay contacts (RY15) |
Battery Banks | 2 banks (A & B) |
Output OK | Relay contacts (RY13) |
Temperature Sense (Optional) | By NTC |
Working Temperature | -20°C ~ +60°C (Refer to output load derating curve) |
Working Humidity | 20 ~ 90% RH non-condensing |
Storage Temperature, Humidity | -40°C ~ +85°C, 10 ~ 95% RH |
Temperature Coefficient | ±0.05%/°C (0 ~ 50°C) |
Vibration | 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
Withstand Voltage | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
Isolation Resistance | I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC 25°C 70%RH |
Safety Standards | UL1012, TUV EN60335-1, EN60335-2-29 (except for 48V) approved |
EMC | Compliance to EN55022 (CISPR22); EN61000-3-2,-3; ENV50204; |
EN61000-4-2,3,4,5,6,8,11; EN55024; light industry level, criteria A | |
MTBF | 135.6Khrs min. MIL-HDBK-217F (25°C) |
Dimensions | 230 x 158 x 67mm |